AS/NZS 3012 construction schedule

How often should equipment be tested?

AS/NZS 3012:2019 applies to electrical installations and equipment used on construction and demolition sites. The intervals below summarise its periodic verification schedule. They are maximum intervals, and a site risk assessment or regulator may require more frequent checks.

Equipment or testMaximum intervalWhat is requiredWho performs it
Construction wiring, including switchboardsBefore energisation, then every 6 monthsInitial inspection and testing, followed by periodic visual inspection.Licensed electrical worker
Relocatable structures, fixed equipment and transportable equipmentEvery 6 monthsPeriodic inspection and verification for continued safe service.Qualified person
Portable equipment, power tools, flexible cords, extension leads and portable socket outlet assembliesEvery 3 monthsInspect, electrically test and tag using the applicable AS/NZS 3760 methods.Competent person or licensed electrical worker
Equipment in site offices and amenitiesEvery 3 monthsThe construction site interval still applies to electrical equipment in these areas.Competent person or licensed electrical worker
Portable RCD push button testAfter connection and before use, at least daily when in useUse the built in test button to confirm that the RCD trips.User
Portable RCD operating time testEvery 3 monthsMeasure the RCD operating time with an RCD tester.Competent person or licensed electrical worker
Fixed RCD push button testEvery monthUse the built in test button to confirm that the RCD trips.User or site representative
Fixed RCD operating time testEvery 12 monthsMeasure the RCD operating time with an RCD tester.Competent person or licensed electrical worker
Hire equipmentInspect before each hire and test at least monthlyBefore supply, inspect prior to each hire and electrically test at intervals no greater than one month. If the equipment remains on site, apply the Table 6 interval for its equipment class.Hire provider and site duty holder

Important: New equipment must be checked for obvious damage before first use. Equipment must also be inspected and tested before returning to service after repair or servicing that could affect electrical safety. Failed or damaged equipment must be removed from service and dealt with under the site safety process.

This table is a plain English summary, not a substitute for reading AS/NZS 3012:2019 in full or obtaining advice for a particular site. For workplaces outside construction and demolition, testing intervals are determined under the applicable requirements, including AS/NZS 3760:2022.

Sources: SafeWork NSW guidance aligned with AS/NZS 3012:2019, WorkSafe Victoria construction electrical guidance, and WorkSafe Victoria guidance referencing AS/NZS 3012:2019.